Fire safety glossary

Fire door

Definition

A fire door is a door assembly — door leaf, frame, seals, and ironmongery — that has been tested and certified to resist the passage of fire and smoke for a specified period. It forms part of a building's passive fire protection, containing fire within the compartment of origin and protecting escape routes. A fire door must always be kept closed (or connected to an automatic hold-open device) to perform its function.

Fire resistance ratings

Understanding FD30, FD60, and the S suffix

FD30

30 minutes fire resistance

Standard for most residential and commercial applications — flat entrance doors, stairwell doors, corridor doors.

FD30S

30 min + smoke seals

Most common specification for UK residential common areas and flat entrance doors. The S suffix indicates fitted smoke seals.

FD60

60 minutes fire resistance

Required in higher-risk locations — plant rooms, high-risk storage areas, some high-rise or commercial applications.

FD60S

60 min + smoke seals

Highest common specification — used in high-rise residential, healthcare settings, and high-risk commercial premises.

Door assembly

The six components of a fire door assembly

01

Door leaf

The door itself — must be a certified fire-resisting construction, typically solid-core timber or steel.

02

Door frame

Must be part of the tested assembly. A fire-rated door in a non-rated frame loses its certification.

03

Intumescent seals

Fitted around the door edge — expand when heated to seal the gap between door and frame against flames and hot gases.

04

Smoke seals

Brush or fin seals that limit cold smoke passage. Required in FD30S / FD60S rated assemblies.

05

Self-closing device

A door closer that returns the door to the closed position automatically after use. Mandatory in fire doors.

06

Ironmongery

Hinges, handles, locks, and vision panels must all be part of the tested assembly or separately rated.

How a fire door protects occupants

Fire doors work through compartmentation — dividing a building into fire-resisting compartments so that a fire in one area cannot spread quickly to others. This is what allows people in other parts of a building to evacuate while the fire is still contained. Research from UL's Close Before You Doze study demonstrated that a closed door — even a standard interior door — dramatically reduces temperatures and toxic gas concentrations in adjacent spaces. A certified fire door provides far greater protection. See our flashover glossary entry for the fire development context.

The "always closed" rule

A fire door only works when it is closed. An open fire door is simply a gap in the compartmentation strategy — fire, smoke, and toxic gases travel freely through it. Wedging or propping fire doors open with furniture, rubber wedges, or cable ties is a common and serious violation found in fire safety audits. In UK workplaces and residential blocks, it is a legal breach of the RRO 2005. If a door must remain open for operational reasons, install an electromagnetic hold-open device linked to the fire alarm — it will release automatically when the alarm sounds.

Check the gap

The gap between the door leaf and frame (and floor) should be no more than 3 mm on all sides when closed. A larger gap allows fire and smoke to pass through before the intumescent seals have had time to expand. Test with a 3 mm coin — if it passes through easily, the door needs adjustment or replacement seals.