Glossary — Passive Fire Protection
Fire Stopping
Fire stopping seals the gaps that building services — pipes, cables, and ducts — create in fire-resisting elements. Without it, compartmentation is theoretical. Every unstopped penetration is a direct fire and smoke path between compartments.
Definition
Fire stopping — materials and systems used to seal penetrations, gaps, and joints in fire-resisting elements so that the required fire resistance (typically 30 or 60 minutes) is maintained across the entire element, including at service penetrations. Required under Approved Document B (Building Regulations) and enforced under the RRO 2005 as part of the fire risk assessment.
Common fire stopping materials and applications
| Material | Application | Standard |
|---|---|---|
| Intumescent sealant | Sealing cable and pipe penetrations through fire-resisting walls; expands on heat to block opening | BS EN 1366-3 |
| Intumescent collars | Around plastic pipes — the collar crushes the pipe as it expands when heated | BS EN 1366-3 |
| Mineral wool / rockwool board | Filling larger voids; duct penetration packing; between joists at party walls | BS EN 1363-1 |
| Fire-rated board (calcium silicate, etc.) | Capping service voids; fire-rated boxing around ductwork | Tested to EI classifications |
| Intumescent pillows / bags | Cable tray bundles passing through walls; flexible bundled cables | Site-applied; BS EN 1366 |
The relationship with compartmentation
Fire stopping is the implementation detail that makes fire compartmentation work in practice. A compartment can be perfectly designed — fire-resisting walls, floors, and fire doors — and still fail at the first penetration if fire stopping is absent. In high-rise residential buildings, the building safety investigations triggered by the Grenfell Tower fire identified fire stopping deficiencies as among the most common active remediation requirements.
Intumescent products: how they work
Intumescent materials expand dramatically when exposed to heat — typically beginning at around 150–200°C. An intumescent sealant around a plastic pipe will remain flexible at ambient temperature; when fire heats the surrounding area, the sealant expands to fill the void left as the plastic pipe melts. Without an intumescent product, the melted pipe leaves an open hole. The test standards (BS EN 1366 series) verify that products maintain integrity for their rated period after the pipe has been destroyed.
Common inspection failures
- Penetrations cut for cables or pipes and never sealed
- Intumescent collars missing from plastic pipes in ceilings of lower floors
- Fire stopping disturbed by subsequent maintenance works and not reinstated
- Rockwool packing that has compressed or been removed
- Open service voids communicating between floors, visible through inspection hatches
For high-rise and flat fire safety context where fire stopping is most critical, see our fire safety for flats guide and our high-rise fire safety 2026 article.